Document Type
Article
Rights
Available under a Creative Commons Attribution Non-Commercial Share Alike 4.0 International Licence
Disciplines
Electrical and electronic engineering
Abstract
Islanding or nonislanding events in grid-connected distributed generation bring along a typical distinguishable transient signature in its frequency profile. This demarcation leads to the development of a new islanding protection approach, which is based on the estimation of frequency waveform parameter (transient's frequency) by Matrix pencil (MP) method. To demonstrate the efficacy of the proposed MP method, four critical scenarios are considered in this paper for covering all possible disturbance events. These events are also compared along with a discrete wavelet transform (DWT) based islanding detection method in simulations as well as in RT-LAB-based real-time environment. It is noteworthy to mention that the proposed MP method has been found to have a positive edge over the DWT-based method in terms of robustness and chances of misidentification.
DOI
https://doi.org/10.1109/TIE.2018.2878125
Recommended Citation
S. Agrawal, S. Patra, S. R. Mohanty, V. Agarwal and M. Basu, "Use of Matrix-Pencil Method for Efficient Islanding Detection in Static DG and a Parallel Comparison With DWT Method," in IEEE Transactions on Industrial Electronics, vol. 66, no. 11, pp. 8937-8946, Nov. 2019, doi: 10.1109/TIE.2018.2878125.
Publication Details
IEEE Transactions on Industrial Electronics